In response to strong customer interest and an increasing number of cooling applications requiring multiple air conditioners on a single cabinet, Kooltronic has developed the KLLC100 Lead-Lag Controller, an option for use with all Kooltronic air conditioners equipped with a 24V relay and external connection (option "D").
This true dual-stage device allows users to control the operation of up to two air conditioners based on either temperature or run-time. For users with fluctuating heat loads, the Lead-Lag Controller will bring the second air conditioner on-line as the heat load increases, and shuts it down as the demand for additional cooling diminishes. It can also be used to distribute the run-time over multiple units, balancing the service life of the air conditioners.
Applications using more than one air conditioner on a cabinet, either for extreme heat load or as a redundant system are becoming more prevalent. Adding a Lead-Lag Controller is an effective solution for users who need to maintain a critical cabinet temperature without interruption or failure.
The Controller features an LED display to indicate which air conditioner is on the run cycle and whether a unit is in the cooling or heating mode, if so equipped. There is also an easy-to-read display panel that provides options to tailor the control of the air conditioners to suit any application. Other standard features include a built-in thermostat with adjustable set-point, deadband and sequencer and a universal mounting plate for simple installation within the cabinet.
STANDARD FEATURES
SPECIFICATIONS
True Dual Stage control
Regulates 1 or 2 air conditioners
Controls units based on temperature and run-time
Second unit can heat or cool only when necessary
Built-in thermostat (adjustable setpoint, deadband and sequencer)
OUTPUT
Type: Triac
Number: Four (4)
Rating: 2 amps per output @ nom. 24 VAC
OPERATIONAL
HEAT/COOL STAGING
First Stage Heat (H1): deadband setting above thermostat setpoint (C1)
Second State Heat (H2): 2°F above H1
First Stage Cool (C1): equal to thermostat
setpoint
Second Stage Cool (C2): 2°F below C1
DEADBAND
Adjustable: 2° to 20°F
SHORT-CYCLE PROTECTION
Stage 1: Three (3) minutes
State 2: Four (4) minutes
SETPOINT
Adjustable: 55 to 90°F @ C1
ADVANCE SEQUENCER
Pin selectable: Alternates every 1, 3, 7, 15
or 28 days, or fixed
Manual ADVANCE pushbutton initializes
sequence record
MODE MEMORY
On power loss, system 'remembers' which
previous mode it was in
TEST MODES
Thermistor bypass calibration mode jumper
Accelerated test mode jumper
DISPLAY LEDs
Green LEDs: call for COOL (C1 & C2)
Red LEDs: call for HEAT (H1 & H2)
GENERAL ARRANGEMENT DRAWING (click and drag to pan)
Dimensions, inches [mm], are for reference only and subject to change.