KPHE39 Water-to-Air
Panel-Mounted Heat Exchangers
Download
Product
Information
TECHNICAL DATA
Click to
Request
Quote
Model
Volts
Power
Maximum
Inlet
Water
Temp. °F
°(C)
Perforance
Watts/°F
(Air In)
Approx
Weight lbs.:
Amps
Watts
1GPM
2GPM
KPHE39
115
2
235
85
68/109
79/142
50
K2PHE39
230
1
235
85
68/109
79/142
50
60 Hz. operation. For 50 Hz. operation, consult Kooltronic.
Click on image for larger view
NEMA
TYPE 12 AND 3R
MAINTAINED
TECHNICAL DATA
Click to
Request
Quote:
Model
Number:
KPHE39
K2PHE39
Volts:
115
230
Power, Amps:
2
1
Power, Watts:
235
235
Max Inlet Water
Temp. °F(°C):
85
85
Perforamce, Watts/°F
(Air in), 1GPM:
68/109
68/109
Perforamce, Watts/°F
(Air in), 2GPM:
79/142
79/142
Approx. Weight lbs.:
50
50
60 Hz. operation. For 50 Hz. operation, consult Kooltronic.
STANDARD FEATURES
Baked Powder Finish
Precision ball bearing motors
Closed-Loop Cooling
The enclosure interior airflow system is isolated from the ambient airflow or waterflow system. No ambient air can invade the cool, dehumidified sensitive component compartment.
Heavy-Duty Steel Shell with Baked Powder Finish
NEMA 12 & 3R Ratings Maintained (UL50)
All units are fully gasketed for tight, leakproof installation, in compliance with the NEMA 12 and 3R Enclosure Ratings.
Six-Foot [1.8m] (minimum) 3-Wire Power Cord
UL/CUL Listed
ACCESSORIES AND OPTIONS
Automatic Water Flow Control
This control consists of a temperature control thermostat and a solenoid valve. When the temperature within the enclosure drops below the thermostat set point due to decreased load or decreasing water temperature, the thermostat closes the solenoid valve. When the temperature increases to the set point (plus a differential) the thermostat opens the solenoid valve and the supply water cools the enclosure. In most models the Automatic Water Flow Control also includes a bypass flow meter which allows a small amount of water (0.25 gpm) to pass through the heat exchanger at all times.
Temperature Alarm
A thermostat is mounted inside the cabinet and attached to a sensor in the warm air return. When the air temperature increases to the set point, a signal is sent to a terminal block. User-installed wiring from the terminal block to local and/or remote warning devices (light, bell, siren, etc.) can be for normally open or closed operation.
Excess Heat Detector
High Water Level Detector
Closes water-supply valve to prevent flooding if excess water accumulates in the drain pan. Signal circuit activates a user-supplied warning device. The low voltage power for the signal circuit is supplied by the user.
Internal Corrosion Protection
This protection increases reliability in hostile environments. This protection for the refrigeration system consists of an air cured coating applied to the brazed joints on the condenser side, providing a degree of protection from corrosive environments. This coating will withstand 1000 hours of salt spray per the ASTM B 117 test method. Also see Stainless Steel Cabinet or GuardianX Air Conditioners. NOTE: Severe operational environments such as waste water treatment and salt spray are likely to cause corrosion failure over a period of time regardless of coating. Warranty: Corrosive conditions may affect the warranty coverage. Consult factory for warranty limitations in corrosive environments. NOTE: For additional corrosion protection options, contact factory.
Low Airflow Detector
Similar to the Airflow Switch shown in the Blower Accessories Section, the switch is installed in a suitable location in the air conditioner to detect loss of airflow, and sends a signal to a terminal block, through which user-installed wiring and warning devices are activated.
Mounting Hinge
(Left-hand or Right-hand) Allows the air conditioner itself to be used as a cabinet door. (Caution: The cabinet must be able to support the full weight of the unit in open position.) Specify left-hand (LH) or right-hand (RH), determined by facing the mounting side of the heat exchanger.
Other voltages and frequencies
Parallel Water Connections
Special materials or finishes
Special motors~ line cords or connectors
Stainless or Aluminum Shell
Water Hook-up Opposite Side
AIRFLOW
Click on image for larger view
GENERAL ARRANGEMENT
Click on image for larger view
Dimensions, inches [mm], are for reference only and subject to change.
GENERAL ARRANGEMENT
Click on image for larger view
Dimensions, inches [mm], are for reference only and subject to change.
SIMILAR MODELS
Model
Guideline
Dimensions
(H x W x D)*
Watts/°F
KPHE32
32.00 x 15.50 x 10.95
80
*See model specifics for drawings, dimensions, mounting or cutout plans.
DOCUMENTS
GA Drawing
KPHE39 General Arrangement Drawing
KPHE39-33 General Arrangement Drawing
KPHE39-XX50 General Arrangement Drawing
Literature
Condensate Evaporator Kits
Increasing the Lifespan and Reliability of Electrical Components
KLLC100 Lead-Lag Controller (1 page)
Kooltronic Design Guide/Catalog (215 pages)
Kooltronic Standard Warranty
NEMA Enclosure Ratings
Short-Form Catalog (16 pages)
Heat Exchanger Quick-Sheet
Operator's Manual
KLLC100 Lead-Lag Controller
KLLC480 Lead-Lag Controller
KPHE36, 39 & 40A Operator's Manual
Wiring Diagram
KPHE39 Wiring Diagram
KPHE39-29, KPHE39-30, KPHE39-X130 Wiring Diagram
KPHE39-33 Wiring Diagram
KPHE39-35 Wiring Diagram
KPHE39CDM Wiring Diagram
KPHE39CDM Wiring Diagram
KPHE39CDMW Wiring Diagram
KPHE39CDMW Wiring Diagram
KPHE39CW Wiring Diagram
KPHE39CW Wiring Diagram
KPHE39DW Wiring Diagram