Hazardous Location Series HL56LV
Class 1 Division 1 and 2 Air Conditioners
Download
Product
Information
TECHNICAL DATA
Click to
Request
Quote
Model
NEMA
Rating
UL/CUL
Listed or
Recognized
BTU/H
Capacity
95/95
Rating
BTU/H
Ambient Temp.
Volts
Hz
Running
Amps
Approx.
Weight
°F
°C
Max./Min.
Max./Min.
lbs
kg
K3A4C12HL56LV
4/4X
Listed
12000
10940
125/-20
52/-28
480
60
6.0
237
108
Rating shown is for operation at maximum ambient temperature.
Pressurized Compartment Volume is 10.8 cu. ft., Air Leakage @ 0.25 i.w.g Pressure is 0.4 CFM
Click on image for larger view
NEMA
NEMA 12, 3R & 4/4X
MAINTAINED
U.S. Patent No.
9,157,670 B2
TECHNICAL DATA
Click to
Request
Quote:
Model
Number:
K3A4C12HL56LV
NEMA
Rating:
4/4X
UL/CUL
Listed or
Recognized:
Listed
BTU/H
Capacity:
12000
95/95 Rating
BTU/H:
10940
Ambient
Temp °.F
Max./Min.:
125/-20
Ambient
Temp °.C
Max./Min.:
52/-28
Volts:
480
Hz:
60
Running
Amps:
6.0
Approx.
Weight lbs.:
237
Approx.
Weight kg.:
108
Rating shown is for operation at maximum ambient temperature.
Pressurized Compartment Volume is 10.8 cu. ft., Air Leakage @ 0.25 i.w.g Pressure is 0.4 CFM
STANDARD FEATURES
All models UL Listed and Recognized
All models UL Listed per 484, Special Purpose Air Conditioners. All models UL Recognized per NFPA 496: 2013, Purged and Pressurized Enclosures for Electrical Equipment. Meets NEC Class I Division 1, Groups A, B, C and D Hazardous Locations, when used with an approved Type X Purge System on the electrical enclosure. Meets NEC Class I Division 2, Groups A, B, C and D, Hazardous Locations when used with an approved Type Z Purge System on the electrical enclosures. Temperature Classification is T-4, 275°F/135°C.
Closed-Loop Cooling
The enclosure interior airflow system is isolated from the ambient airflow or waterflow system. No ambient air can invade the cool, dehumidified sensitive component compartment.
Compressor Short Cycle Protector
Protects the compressor from possible damage due to harmful short cycling, (frequent starting) where temperature controls enable the compressor to restart frequently or after a power interruption. These conditions could be due to low or fluctuating heat loads within the electrical enclosure or a power failure. The Compressor Short Cycle Protector will prevent the compressor from starting when it has been shut off for less than several minutes or the power was interrupted. By limiting the number of compressor starts per hour, the life of the compressor is prolonged. It is recommended where installations are subject to solar gain and or changes in the enclosure internal load due to the degree of usage of the equipment being cooled. It is also recommended where higher capacity units are specified in anticipation of the future addition of heat producing equipment being added to the enclosure.
Filter
All KOOLTRONIC filters consist of a multi-layer grid of sturdy corrugated aluminum, securely held in a one-piece aluminum frame. Filters are required wherever air is drawn into an electronics enclosure or related cooling equipment to keep internal parts as clean as possible. A non-drying adhesive coating traps a high percentage of particulate matter. These filters are reuseable, they may be washed and recoated with the appropriate filter recoating adhesive. Replacements are available for those which become damaged or otherwise non-serviceable.
Interior and Exterior Purge Connections
Internal Corrosion Protection
NOTE: Internal Corrosion Protection is a Standard Feature on NEMA 4X models only. This protection for the refrigeration system consists of an air cured coating applied to the brazed joints on the condenser side, providing a degree of protection from corrosive environments. This coating will withstand 1000 hours of salt spray per the ASTM B 117 test method. Also see Stainless Steel Cabinet or Integrity NEMA 4/4X Air Conditioners. NOTE: Severe operational environments such as waste water treatment and salt spray are likely to cause corrosion failure over a period of time regardless of coating. Warranty: Corrosive conditions may affect the warranty coverage. Consult factory for warranty limitations in corrosive environments. NOTE: For additional corrosion protection options, contact factory.
Maintains NEMA 12, 3R & 4/4X Ratings (UL50)
Maintains NEMA Type 12, 3R & 4/4X Enclosure Ratings.
Painted Condenser and Evaporator Coils
Pressure Compensation Terminal Block
Allows user to attach auxiliary pressure supply.
Programmable Temperature Alarm
All models feature a programmable temperature alarm to alert if early action is required.
Programmable Thermostat
All models feature a programmable thermostat, allowing more accurate and versatile performance features.
Shock and Vibration Resistance
Hazardous Location Series models are designed to withstand shock and vibration in two different planes for a minimum of 4 hours per plane at 1G acceleration.
Stainless Steel Shell
For applications in corrosive or other hostile environments such as those requiring Internal Corrosion Resistant Coatings, especially where chemical/moisture combinations are present.
Zero ODP Refrigerant
R410a, an HFC having zero ozone depleting potential.
ACCESSORIES AND OPTIONS
Enclosure Heater
Eliminates damaging condensation, increasing reliability of electrical enclosure components.
Filter Recoating Adhesive
This compound is a superior product for recoating filters after washing. The adhesives penetrate dirt layers to keep the filter surface tacky for longer effective performance between washings.
Lead-Lag Controller
Remote Monitoring
An optional feature for models with Programmable Thermostat, Remote Monitoring provides temperature data for warning of early action required.,Accomplished through a Hot Key connection from the Programmable Thermostat to a monitoring system (not supplied) that is ModBus-RTU compatible (i.e. XWEB500/3000/300) via an external 2-position terminal block.
Remote Thermostat Relay
Used only with a user-installed remote thermostat or the Kooltronic KLLC100 Lead Lag Controller, this 24VAC relay can be used for the sequential operation of two units or with a single unit. An external terminal strip is provided for field interconnection. NOTE: User-installed thermostat must have a set point of 75°F with a differential of 11°F. NOTE: A factory installed thermostat is not provided with this option.
Replacement Filters
All KOOLTRONIC filters consist of a multi-layer grid of sturdy corrugated aluminum, securely held in a one-piece aluminum frame. Filters are required wherever air is drawn into an electronics enclosure or related cooling equipment to keep internal parts as clean as possible.,A non-drying adhesive coating traps a high percentage of particulate matter. These filters are reuseable, they may be washed and recoated with the appropriate filter recoating adhesive. Replacements are available for those which become damaged or otherwise non-serviceable.
For
Hazardous Location Series HL56LV 480 Volt 3-Phase
models the filter part number is
1524F
.
AIRFLOW
Click on image for larger view
PERFORMANCE
GENERAL ARRANGEMENT
Click on image for larger view
Dimensions, inches [mm], are for reference only and subject to change.
GENERAL ARRANGEMENT
Click on image for larger view
Dimensions, inches [mm], are for reference only and subject to change.
Many popular units are available as 3D solid models for customer system integration. Contact Kooltronic for details
.
DOCUMENTS
2-D Drawing of the Mounting Plan
K3A6C12HL56LV 2-D Drawing of the Mounting Plan [48Kb]
3-D Solid Model
K3A6C12HL56LV 3D Solid Model [15361Kb]
Brochure
Hazardous Location Series Brochure [425Kb]
Data Sheet
KLLC100-480 Lead-Lag Controller Product Data Sheet [58Kb]
Hazardous Location Series K3A6C12HL56LV Data Sheet [373Kb]
GA Drawing
HL56LV General Arrangement Drawing [96Kb]
HL56LV General Arrangement Drawing [92Kb]
Literature
Air Conditioner Quick-Sheet [105Kb]
Condensate Evaporator Kits [241Kb]
Condensation and Electronics [3983Kb]
Electronic Enclosure Cooling With Special Purpose Air Conditioners [254Kb]
Hazardous Location Series White Paper [234Kb]
Increasing the Lifespan and Reliability of Electrical Components [212Kb]
KLLC100 Lead-Lag Controller (1 page) [58Kb]
Kooltronic Custom Capabilities Flyer [2194Kb]
Kooltronic Design Guide/Catalog (215 pages) [24440Kb]
Kooltronic Refrigeration System Manufacturing [55Kb]
Kooltronic Standard Warranty [55Kb]
NEMA Enclosure Ratings [91Kb]
Short-Form Catalog (16 pages) [897Kb]
Airflow Switch Data Sheet [159Kb]
Laboratory Environmental Testing Services [157Kb]
Powder Paint Application Facilities Flyer [165Kb]
Operator's Manual
KLLC100 Lead-Lag Controller [38Kb]
KLLC480 Lead-Lag Controller [79Kb]
Hazardous Location Series K3A6C12HL56LV Operator's Manual [820Kb]
Wiring Diagram
Hazardous Location Series K3A6C12HL56LV Wiring Diagram (Ladder) [56Kb]
Hazardous Location Series K3A6C12HL56LV Wiring Diagram (Ladder) [61Kb]
Hazardous Location Series K3A6C12HL56LV(G) Wiring Diagram (Point-to-Point) [89Kb]
Hazardous Location Series K3A6C12HL56LV(G) Wiring Diagram (Point-to-Point) [81Kb]
Hazardous Location Series K3A6C12HL56LV(G) Wiring Diagram (Point-to-Point) [90Kb]
Hazardous Location Series K3A4C18HL58LV & 56LV (G) Wiring Diagram (Point-to-Point) [78Kb]
Hazardous Location Series K3A4C18HL58LV & HL56 Wiring Diagram (Ladder) [58Kb]